# Do vacuum and AGSS pumps deliver more flow at 60 Hz?

**Does a medical vacuum or anaesthetic gas scavenging pump deliver a different flow on a 60 Hz supply than on 50 Hz?**

Yes: in the ULTRAVAC and ULTRASEG datasheets every vacuum and AGSS pump model is listed with a higher capacity at 60 Hz than at 50 Hz, for example 3x60 instead of 3x50 m³/h for an ULTRAVAC 3.50/500 and 60 instead of 50 m³/h for an ULTRASEG E50.

Both datasheets print a 50 Hz and a 60 Hz capacity column side by side for each model, so the same model has two capacity figures. The ULTRASEG table also gives the motor power at each frequency; the ULTRAVAC table gives motor power at 50 Hz only.

## ULTRASEG anaesthetic gas scavenging, per pump

| Model | Capacity at 50 Hz (m³/h) | Capacity at 60 Hz (m³/h) | Motor at 50 Hz (kW) | Motor at 60 Hz (kW) |
|---|---|---|---|---|
| H50 | 50 | 58 | 0,55 | 0,63 |
| E50 | 50 | 60 | 0,2 | 0,23 |
| E100 | 103 | 120 | 0,4 | 0,5 |
| H170 | 170 | 195 | 2,2 | 2,55 |
| E300 | 315 | 376 | 2,2 | 2,55 |

## ULTRAVAC medical vacuum, triplex plants

| Model | Capacity at 50 Hz (m³/h) | Capacity at 60 Hz (m³/h) | Motor power at 50 Hz, three-phase (kW) |
|---|---|---|---|
| 3.10/200 | 3x10 | 3x12 | 3x0,37 |
| 3.25/500 | 3x25 | 3x30 | 3x0,75 |
| 3.50/500 | 3x50 | 3x60 | 3x1,25 |
| 3.100/1000 | 3x110 | 3x132 | 3x3,0 |
| 3.300/1000 | 3x300 | 3x360 | 3x7,5 |

Rows selected from the full tables in the ULTRASEG and ULTRAVAC datasheets, as printed. Ultra Controlo engineering confirms the configuration for each project.

## Voltage and frequency in the Ultra Controlo datasheets

- ULTRASEG: motor voltage 200 to 240 V Δ / 345 to 415 V Y at 50 Hz and 220 to 275 V Δ / 380 to 480 V Y at 60 Hz; the datasheet states that other voltages and frequencies are supplied according to the country regulations.
- ULTRAVAC: the datasheet text gives motor power of 0.37 to 40 kW, 400 V, 50 Hz.
- ULTRALOBO LPT oxygen boosters: 400 V/50 Hz, other on request.
- ULTRAGEC 4 emergency cabinet: 230 V / 50 Hz.

For PSA oxygen plants, see [does 50 Hz or 60 Hz matter for an oxygen plant](https://library.ultracontrolo.com/answers/does-50-or-60-hz-matter-for-an-oxygen-plant/). For the AGSS model in the first table, see ULTRASEG E50.

### Does the ULTRAVAC datasheet give motor power at 60 Hz?

No. Its table gives motor power at 50 Hz only, for three-phase and single-phase motors.

### Can ULTRASEG be supplied for a 60 Hz network?

The ULTRASEG datasheet lists 60 Hz capacities and motor voltages, and states that other voltages and frequencies are supplied according to the country regulations.

## Sources

- [ULTRASEG datasheet, p. 3 and p. 5](https://www.ultracontrolo.com/products/ultraseg)
- [ULTRAVAC datasheet, p. 2 and p. 5](https://www.ultracontrolo.com/products/ultravac)
- [ULTRALOBO LPT datasheet, p. 3](https://www.ultracontrolo.com/products/ultralobo)
- [ULTRAGEC datasheet, p. 4](https://www.ultracontrolo.com/products/ultragec)

Reviewed: 2026-10-27. Ultra Controlo engineering. https://library.ultracontrolo.com/answers/how-does-60-hz-change-vacuum-and-agss-pumps/