# How noisy is a medical vacuum plant?

**How noisy is a medical vacuum plant, and how is the noise controlled?**

Under HTM 02-01 (2026), the NHS England guidance, the free-field noise outside a plantroom rises by 5 dBA for each additional vacuum pump running, over and above the specified limits, so plantroom noise is handled in the design, including silencing the pump discharge where needed.

HTM 02-01 asks for plantrooms designed and constructed to ensure satisfactory control of noise emission. It gives no single noise limit for a hospital vacuum plant: free-field noise levels should be provided to support the acoustic design of the plantroom.

## Noise control measures in HTM 02-01

- Acoustic enclosures should be considered to reduce free-field noise in noise-sensitive areas next to the plantroom; enclosures and plantroom design should not inhibit normal cooling or maintenance (17.146 and 17.147).
- The discharge from some vacuum pumps may require silencing (17.149). Noise from the vacuum exhaust should be subject to a risk assessment, and a silencer should be installed where there is potential for noise issues (10.29); see [where medical vacuum exhaust should discharge](https://library.ultracontrolo.com/answers/where-should-medical-vacuum-exhaust-discharge/).
- Pipework and electrical conduits connected to the plant should have flexible connectors where necessary, and pumps should sit on suitable anti-vibration mountings where necessary, to limit the transfer of noise and vibration (17.151 and 17.153).

## Dental vacuum plant

For dental vacuum plant in a typical plant room, HTM 02-01 (11.17) considers these free-field levels at 1 m as maxima: 75 dBA below 5 kW, 82 dBA from 5.1 to 15 kW and 89 dBA above 15 kW. It adds that smaller plant produces much lower levels, with a typical 64 dB(A) for a single chair unit combining pump, separator and amalgam separator (11.18), and that acoustic screening, typically giving a 10 dB(A) reduction, may be added if desired (11.19). These maxima are for dental plant and not for hospital medical vacuum plant. See [what a dental central suction system is](https://library.ultracontrolo.com/answers/what-is-a-dental-central-suction-system/).

## Noise figures on the Ultra Controlo product pages

The ULTRAVAC product page gives a noise level of 60 to 81 dB(A) per pump, and its table of plants with 3 pumps in the ST version repeats that figure per pump, with each size available with 1 to 6 pumps. The page does not state the measuring distance, and the figures are per pump, not for a complete plant or for the level outside a plantroom.

| Plant | Pump | Capacity m³/h | Motor kW | Noise dB(A) per pump |
|---|---|---|---|---|
| ULTRAVAC 3.10/200 ST | VGD 10 | 3 × 10 | 3 × 0.45 | 60 |
| ULTRAVAC 3.100/1000 ST | VCS 100 | 3 × 100 | 3 × 3.0 | 65 |
| ULTRAVAC 3.1100/2000T ST | VCS 1100 | 3 × 1,100 | 3 × 30 | 81 |

The ULTRAVAC CLP product page gives air cooling and a noise level of 78 to 82 dB by model, printed in dB: CLP 1.60 (60 m³/h, 1.1 kW) at 78 dB and CLP 1.1000 (950 m³/h, 18.5 kW) at 82 dB.

### Does a second vacuum pump make the plantroom louder?

HTM 02-01 (2026) says that when two vacuum pumps or compressors run together in a duplex installation, and three or more in a multiplex one, the free-field noise level outside the plantroom increases by 5 dBA for each additional machine operating, over and above the specified limits.

### Can acoustic screening reduce the noise of a dental vacuum plant?

HTM 02-01 (2026) says acoustic screening, typically giving a 10 dB(A) reduction in noise level, may be added to dental vacuum plant if desired.

## Sources

- [NHS England, HTM 02-01 Medical gas pipeline systems (2026), Part A, paragraphs 10.29, 11.17 to 11.19 and 17.145 to 17.153](https://www.england.nhs.uk/wp-content/uploads/2016/05/health-technical-memorandum-02-01-medical-gas-pipeline-systems-part-a-design-installation-validation-verification-aug-2026.pdf)
- [ULTRAVAC product page (technical specifications and 3-pump ST table)](https://www.ultracontrolo.com/products/ultravac)
- [ULTRAVAC CLP product page (technical specifications and model table)](https://www.ultracontrolo.com/products/ultravac-clp)

Reviewed: 2026-11-18. Ultra Controlo engineering. https://library.ultracontrolo.com/answers/how-noisy-is-a-medical-vacuum-plant/