# Should the dryer go before or after the air receiver?

**Should a compressed air dryer be installed before or after the air receiver?**

The 2016 US DOE sourcebook describes two differing points of view on where to put the primary air receiver relative to the dryer, and says one way to resolve it is to install storage both upstream and downstream of the dryer, with the downstream storage equal to or larger than the upstream storage.

The sources do not give one rule. Each describes what a receiver on either side of the dryer does, and two of them disagree on which position is usual.

## Receiver before the dryer

The 2016 US DOE sourcebook (storage fact sheet) says that if the receiver is located before the compressed air dryer, it may provide additional radiant cooling and drop out some of the condensate and entrained oil, benefiting the dryer. However, the receiver will be filled with saturated air, and if there is a sudden demand that exceeds the capacity rating of the compressor and matching dryer, the dryer can be overloaded, resulting in a higher pressure dew point.

## Receiver after the dryer

The same fact sheet says that if the receiver is located after the dryer, some of those advantages are lost. The receiver is filled with dried air, so a sudden demand in excess of the compressor and dryer capacity rating is met with dried air; the dryer sees only the output of the compressor, so the pressure dew point is not affected.

## Storage on both sides

The sourcebook says one way to resolve this is to install storage both upstream and downstream of the dryer, remembering that the storage downstream should be equal to or larger than the storage upstream. Compressed Air Challenge Fact Sheet #11 (May 2026) says a best practice is to use multiple receivers: one prior to the dryer (wet receiver) and one directly after it (dry receiver), and that receivers close to points of intermittent use reduce pressure swings.

## Where the two editions differ on the usual position

| Source | What it says about the usual position |
|---|---|
| US DOE sourcebook (2016), Fact Sheet 7 | In most systems the receiver will be located just after the dryer; in some cases it makes sense to use multiple receivers, one prior to the dryer and one closer to points of intermittent use |
| Compressed Air Challenge Fact Sheet #11 (May 2026) | In most systems the receiver will be located before the dryer |

The sourcebook adds that, in any case, the dryer and its associated filters add pressure drop, which must be taken into account when setting the compressor discharge pressure.

## In a medical air plant

HTM 02-01 (2026), the NHS England guidance, says an inline cyclone water separator should be installed between each compressor and the receivers.

### What happens if the receiver is upstream of the dryer?

The 2016 US DOE sourcebook says the receiver may provide additional radiant cooling and drop out some condensate and oil, but it will be filled with saturated air, and a sudden demand above the compressor and dryer rating can overload the dryer and raise the pressure dew point.

### Do the sources agree on which position is usual?

No. The 2016 US DOE sourcebook (Fact Sheet 7) says the receiver is usually just after the dryer, while Compressed Air Challenge Fact Sheet #11 (May 2026) says it is usually before the dryer.

## Sources

- [US DOE and Compressed Air Challenge, Improving Compressed Air System Performance, 3rd edition (2016): Fact Sheet 6, Compressed Air Storage, p. 43 (PDF p. 48); Fact Sheet 7, p. 49 (PDF p. 54)](https://www.energy.gov/sites/prod/files/2016/03/f30/Improving%20Compressed%20Air%20Sourcebook%20version%203.pdf)
- [Compressed Air Challenge, Fact Sheet #11, Proven Opportunities at the Component Level (May 2026), p. 4](https://www.compressedairchallenge.org/data/sites/1/media/library/factsheets2026/fact-sheet-11-proven-opportunities-at-the-component-level_updated2026.pdf)
- [NHS England, HTM 02-01 Part A (August 2026 edition): 7.46 (PDF p. 91)](https://www.england.nhs.uk/wp-content/uploads/2016/05/health-technical-memorandum-02-01-medical-gas-pipeline-systems-part-a-design-installation-validation-verification-aug-2026.pdf)

Reviewed: 2026-11-18. Ultra Controlo engineering. https://library.ultracontrolo.com/answers/should-the-dryer-go-before-or-after-the-air-receiver/