# Medical air vs hospital industrial compressed air

Medical air is a medicine supplied to patients and medical devices through its own pipeline, while hospital industrial (technical) compressed air drives building equipment such as autoclaves and pneumatic systems; the two are built to different specifications and kept separate.

Hospitals use compressed air in two different ways. Medical air drives ventilators, CPAP and other respiratory equipment, and surgical tools when supplied as surgical air; the European Pharmacopoeia treats it as a medicine. Technical air serves the building: the autoclaves for sterilisation and other pneumatic systems. The ACIH datasheet notes that hospital standards prohibit the use of medicinal air for industrial purposes and require an independent supply, which is why the two are separate systems.

## Side by side

|  | Medical air | Hospital industrial (technical) air |
|---|---|---|
| Typical users | Ventilators, CPAP, BiPAP, nebulisers; surgical tools as surgical air | Autoclaves for sterilisation and other pneumatic systems |
| Quality reference | Pharmacopoeia monograph (Ph. Eur. 1238); pharmacopoeial tests include CO, CO2, SO2 and NOx | ISO 8573-1 purity classes for particles, water and oil |
| Portuguese specification | ACSS ET 03/2006 (medical gases and vacuum) | ACSS ET 08/2010 (technical compressed air), minimum class [2:4:2] |
| Regulatory status of the plant | Medical device: ULTRAAR, CE 1639, Class IIb (Directive 93/42/EEC) | Machinery: ACIH complies with the Machinery Directive |
| Ultra Controlo system | ULTRAAR (SC, SCA, ESW, ME) | ACIH |

## What medical air should not be used for

HTM 02-01 (2026), the NHS England guidance, states that medical air is a medicine and should not be used for process purposes such as endoscope dryers. It also says medical air systems should not supply sterilizer chambers or door seals, should not power pendant control and braking systems, and should not supply mechanical services. For pendants it specifies electric brake systems.

## How ACIH is built

ACIH is the Ultra Controlo industrial compressed air system for hospital buildings. It uses rotary screw compressors with air treatment, vertical tanks of 100 to 3,000 litres and a condensate treatment unit that removes oil so the condensate can go to the sanitary network. Its datasheet states that it complies with the Machinery Directive and the ACSS ET 08/2010 specifications, and that it resembles ISO 7396-1 in its redundancy, command, control and alarm systems. On request it can be built with totally oil-free compressors, and adsorption dryers can be added for dew points of −20 °C or −40 °C.

Technical air still has a defined quality. In Portugal, ACSS ET 08/2010 sets ISO 8573-1:2010 class [2:4:2] as the minimum for centrally produced technical compressed air. That class grades particles, water and oil only, and is not a medical air specification.

### Can medical air feed hospital autoclaves?

Not under HTM 02-01, the NHS England guidance, which says medical air systems should not supply sterilizer chambers or door seals. The ACIH datasheet also notes that hospital standards prohibit using medicinal air for industrial purposes.

### Is ACIH surgical or medical air?

No. ACIH is industrial hospital compressed air built to the Machinery Directive and ACSS ET 08/2010 for building equipment.

## Sources

- [ACIH datasheet, p. 2 to 4 and 7](https://www.ultracontrolo.com/products/acih)
- [ULTRAAR SCA datasheet, p. 2; ULTRAAR ESW datasheet, p. 3](https://www.ultracontrolo.com/products/ultraar-sca)
- [NHS England, HTM 02-01 Medical gas pipeline systems, Part A (2026), paras 4.78, 4.85, 4.87, 7.98 to 7.100](https://www.england.nhs.uk/wp-content/uploads/2016/05/health-technical-memorandum-02-01-medical-gas-pipeline-systems-part-a-design-installation-validation-verification-aug-2026.pdf)
- [ACSS, ET 08/2010 V.2025 Especificações técnicas para ar comprimido técnico em edifícios hospitalares](https://www.acss.min-saude.pt/wp-content/uploads/2016/10/ET-08_2010_V.2025_VF.pdf)
- [ACSS, ET 03/2006 v.2024 Especificações técnicas para gases medicinais e aspiração em edifícios hospitalares](https://www.acss.min-saude.pt/wp-content/uploads/2016/10/ET-03_2006_v2024-Gases-medicinais_VF.pdf)
- [ISO 8573-1:2010 (iso.org abstract)](https://www.iso.org/standard/46418.html)
- [EDQM, Ph. Eur. monograph 1238 Air, medicinal](https://extranet.edqm.eu/4DLink1/4DCGI/Web_View/mono/1238)

Reviewed: 2026-10-22. Ultra Controlo engineering. https://library.ultracontrolo.com/compare/medical-air-vs-hospital-industrial-air/