# Artificial demand (compressed air)

Compressed Air Challenge Fact Sheet #4 (May 2026) uses the term artificial demand for the added compressed air demand that appears at elevated system pressure from unregulated uses such as leaks, open blowing and production applications without regulators or with wide open regulators.

The fact sheet (page 1) says this added demand substantially increases energy consumption. It says that, instead of increasing the compressor discharge pressure or adding compressor capacity, alternatives should be sought: reduced pressure drop, strategic compressed air storage, and demand or immediate controls. It adds that equipment should be specified and operated at the lowest efficient operating pressure.

Fact Sheet #6 (page 1) gives the rule that every 2 psi of pressure difference is equal to about a 1% change in energy consumption, and Fact Sheet #4 (page 3) lists reduced leakage rates among the effects of a lower system pressure. See [why pressure drop costs energy](https://library.ultracontrolo.com/answers/why-does-pressure-drop-cost-energy/) and [compressed air leaks](https://library.ultracontrolo.com/industry/compressed-air-leaks/).

## Sources

- [Compressed Air Challenge, Fact Sheet #4: Pressure Drop and Controlling System Pressure (May 2026, Rev. 1), pp. 1 and 3](https://www.compressedairchallenge.org/data/sites/1/media/library/factsheets2026/fact-sheet-4-pressure-drop-and-controlling-system-pressure_updated2026.pdf)
- [Compressed Air Challenge, Fact Sheet #6: Compressed Air System Controls (May 2026, Rev. 1), p. 1](https://www.compressedairchallenge.org/data/sites/1/media/library/factsheets2026/fact-sheet-6-compressed-air-system-controls_updated2026.pdf)

Reviewed: 2026-11-19. Ultra Controlo engineering. https://library.ultracontrolo.com/glossary/artificial-demand/