# Hospital oxygen demand calculator, with the HTM 02-01 flows

NHS England's HTM 02-01 (2026) plans critical care at 60 L/min per bed space with high-flow ventilation, 10 L/min without, and operating suites at 50 L/min for the first operating room plus 10 L/min for each of the others. The calculator adds these flows to your ward figures and converts the total to m³/h.

## What the calculator adds

| Area | Flow used | Source |
|---|---|---|
| Critical care with high-flow ventilation | 60 L/min per bed space, all bed spaces assumed occupied and using oxygen | HTM 02-01 (2026) |
| Critical care without high-flow ventilation | 10 L/min per bed space | HTM 02-01 (2026) |
| Operating suites | 50 L/min for the first operating room and 10 L/min for each of the others | HTM 02-01 (2026) |
| In-patient beds using oxygen | Your flow per bed; HTM 02-01 gives a typical flow of 6 L/min and a design flow of 10 L/min per terminal unit | HTM 02-01 (2026), Table 2 |
| Other areas | Your own figure in L/min |  |

The total in L/min is multiplied by 60 and divided by 1,000 to give m³/h, the conversion WHO used in its 2020 interim guidance, and multiplied by 24 for m³ per day.

## Matching an ULTRAOX ST unit

The calculator then lists the smallest [ULTRAOX ST](https://library.ultracontrolo.com/products/ultraox-st/) models whose capacity per unit, as printed in the ULTRAOX ST datasheet (p. 5), covers the total. ULTRAOX ST models range from 3.10 to 165.3 Nm³/h per unit, supply oxygen at a purity of 93% ± 3%, and the plants are modular and can be expanded without replacing the concentrator. Ultra Controlo engineering confirms the configuration for each project.

## Why this is an estimate

- Flow cannot be predicted precisely. HTM 02-01 states that pipeline flow cannot be predicted precisely, but gives guideline flows that have proved adequate in practice.
- The plant uses some of its own oxygen. HTM 02-01 says PSA regeneration uses a proportion of the product gas, which should be taken into account when sizing the plant.
- Several methods exist. WHO's Foundations of medical oxygen systems (2023) sizes plants from estimated demand, built from beds per type of ward, wall outlets per bed or historical consumption, and warns that counting 100% of the outlets in use at maximum flow can easily oversize the source.
- Today's use is not the need. Open Critical Care warns that current consumption may grossly underestimate optimal consumption, because patients who lack access to oxygen today must also be counted.

The button under the result opens an email to Ultra Controlo with your figures; see also [what information is needed for an oxygen plant quote](https://library.ultracontrolo.com/answers/what-information-is-needed-for-an-oxygen-plant-quote/).

### Does the calculator replace a design?

No. HTM 02-01 states that pipeline flow cannot be predicted precisely, and that the oxygen a PSA plant uses for regeneration should be taken into account when sizing it; the result is a planning figure to discuss with an engineer.

### What flow should I enter for ward beds?

HTM 02-01 gives in-patient accommodation a typical flow of 6 L/min and a design flow of 10 L/min per terminal unit. WHO (2023) notes that average flow rates from clinical guidelines may not represent real practice in the facility.

### Is 60 L/min per critical care bed always needed?

No. HTM 02-01 (2026) reduces it to 10 L/min per bed space where there is no requirement for high-flow ventilation.

## Sources

- [NHS England, HTM 02-01 Part A (2026), paragraphs 4.6, 4.45, 4.49 to 4.51, 4.54, 6.110 and Table 2](https://www.england.nhs.uk/wp-content/uploads/2016/05/health-technical-memorandum-02-01-medical-gas-pipeline-systems-part-a-design-installation-validation-verification-aug-2026.pdf)
- [WHO, Oxygen sources and distribution for COVID-19 treatment centres, interim guidance (4 April 2020), Table 1](https://www.who.int/publications/i/item/oxygen-sources-and-distribution-for-covid-19-treatment-centres)
- [WHO, Foundations of medical oxygen systems (17 February 2023)](https://iris.who.int/server/api/core/bitstreams/4ad6f5fd-089e-4142-8439-b64e98d816d8/content)
- [Open Critical Care, Oxygen FAQ: How do I know how much oxygen my facility is using or needs?](https://opencriticalcare.org/faq/how-do-i-know-how-much-oxygen-my-facility-is-using-or-needs/)
- [ULTRAOX ST datasheet, p. 2, p. 4 and p. 5 (model table); 2026 edition (oxygen purity and model range)](https://www.ultracontrolo.com/products/ultraox-st)

Reviewed: 2026-10-29. Ultra Controlo engineering. https://library.ultracontrolo.com/tools/hospital-oxygen-demand-calculator/