How is a hospital medical vacuum plant sized?

What inputs determine the size of a hospital medical vacuum plant?

Short answer

Under the NHS England guidance HTM 02-01 (2026), a hospital medical vacuum plant is sized from the diversified design flow of the areas it serves, using a design flow per terminal unit and a diversity formula per department; the pumps should still supply that flow during maintenance on any pump plus a further single fault.

Step 1: define the rooms

At design stage the project team defines the requirements of each room or space. HTM 02-01 (2026) notes that pipeline flow cannot be predicted precisely, so it gives guideline values that have proved adequate in practice. In general note II of its annex, Portugal's ACSS ET 03/2006 asks designers to confirm the number of outlets and the real utilisation coefficients, and to apply one of FD S 90-155, HTM 2022, AS 2896-1998 or SIS HB 370 when sizing the distribution; HTM 2022 has since been superseded by HTM 02-01 (2026), and section 16 of the same specification lists AS 2896-2011.

Step 2: apply design flows and diversity

HTM 02-01 gives, for each department, a design flow per terminal unit and a formula for the diversified flow Q. Medical vacuum is typically 40 L/min per terminal unit; each operating room needs 80 L/min because the surgical team and the anaesthetist may use suction together. In the formulas, n is the number of beds, treatment spaces or single rooms where the procedure is performed, not the number of terminal units.

Area (HTM 02-01, Table 10)Design flow per terminal unitDiversified flow Q
Emergency department, resuscitation room (per trolley space)40 L/minQ = 40 + [(n − 1)10]
Operating room80 L/min per room (40 L/min per terminal unit)Q = 80
Critical care areas40 L/minQ = 40 + [(n − 1)10]

For a 28-bed ward unit with single rooms, four-bed rooms and a treatment room, the diversified flow is based on 40 L/min. The pipework is then designed on the diversified flows and the permissible pressure loss.

Step 3: choose the pumps and the vessel

  • Capacity should match the calculated demand (10.5). Pump capacity is stated as free air aspirated in L/min, with the pump at 475 mmHg (63 kPa) and at 450 mmHg (60 kPa) at the plant pipeline connection (10.27).
  • The pumps are arranged so that, during maintenance on any pump and a further single fault, the remaining pumps still supply the system design flow (10.17). See how many pumps a plant needs.
  • The vessel is sized to minimise stop/start cycles, which should stay within the manufacturer's recommendation, typically six per hour (10.19), and the Table 20 note sizes the reservoir's water capacity at a minimum of the total design flow rate. ACSS sets a maximum of 20 starts per hour for each pump.

ULTRAVAC

ULTRAVAC plants are configured with 1 to 12 pumps of 3 to 1,600 m³/h each and vacuum vessels of 24 to 6,000 litres, so the number of pumps and the vessel size can follow the calculated design flow.

More questions

Does a day unit use the same demand basis as a 24-hour hospital?

No. HTM 02-01 (2026) says sites that are not open 24/7 should consider demand across their working hours only.

Is dental suction sized the same way?

No. HTM 02-01 bases dental high volume systems on 300 L/min at each chair cannula connector, with their own diversity rule.