Medical gas library

Industry

Why does a screw compressor trip on high temperature?

Short answer

The Compressed Air Challenge Fact Sheet #5 (May 2026) says inadequate maintenance can lead to high operating temperatures; for a lubricant-injected screw compressor its checklist covers clean heat exchanger surfaces, fans and water pumps, the lubricant, which removes most of the heat of compression, and the cooling water.

In a lubricant-injected rotary screw compressor, the lubricant lubricates bearings, gears and the intermeshing rotor surfaces, acts as a seal and removes most of the heat of compression, according to the Compressed Air Challenge (CAC) Fact Sheet #5 (May 2026). The same fact sheet lists the compressor, heat exchanger surfaces, air lubricant separator, lubricant, lubricant filter and air inlet filter as the main maintenance areas of the package.

What the maintenance guidance points to

AreaWhat CAC Fact Sheet #5 (May 2026) says
Coolers and heat exchanger surfacesThe compressor and intercooling surfaces need to be kept clean and foul-free; fans and water pumps should also be inspected.
LubricantInspect the level daily and top off or replace per manufacturer specifications; only a lubricant meeting the manufacturer's specifications should be used; lubricant can become corrosive.
Lubricant filterChange per manufacturer specifications.
Water coolingCheck water quality (especially pH and total dissolved solids), flow and temperature, and clean or replace filters and heat exchangers per manufacturer specifications.
Operating temperatureVerify that operating temperature is per manufacturer specification.
Drive motorKeep air passages and cooling fins clean; poor motor cooling can increase motor temperature and winding resistance.

Temperature as a maintenance signal

The 2016 DOE sourcebook said temperature measurements help to indicate whether equipment is operating at peak performance, that equipment running hotter than specified parameters is not performing at peak efficiency and requires service, and that for rotary-lubricated compressors the air discharge temperatures must be maintained for reliable compressor performance. It listed inlet air temperature among the measurements to take when baselining a system.

After a trip

The CAC fact sheet says most problems are minor and can be corrected by simple adjustments, cleaning, part replacement or the elimination of adverse conditions. Before any work, the 2016 sourcebook told readers to refer to the manufacturer's manuals for exact procedures and to follow all safety precautions.

ULTRASCREW compressors, supplied by Ultra Controlo, are oil injected rotary screw compressors according to the ULTRASCREW datasheet.

More questions

What does the lubricant do in a screw compressor?

CAC Fact Sheet #5 (May 2026) says it lubricates bearings, gears and intermeshing rotor surfaces, acts as a seal and removes most of the heat of compression.

Which lubricant should be used?

CAC Fact Sheet #5 says only a lubricant meeting the manufacturer's specifications should be used.

Sources

Ultra Controlo figures come from its technical datasheets. Third-party facts were read at the source on the date shown.

Reviewed: · Ultra Controlo engineering · Markdown version

Related