Pressure-reducing station (PRS)
Under HTM 02-01 (2026), the NHS England guidance, a pressure-reducing station (PRS) is the station that should be provided where the pressure needs to be reduced on an air system, for example from surgical air to medical air.
HTM 02-01 (2026) says the PRS should be a duplex system, so that the flow of gas is not interrupted in the event of maintenance or component failure. It should be set up with a lead and lag regulator with a maximum of 50 kPa differential to maintain line pressure.
According to the HTM, each side of the PRS should comprise a pressure regulator, an analogue pressure gauge, a safety relief valve, a terminal unit for testing, a non-return valve and a pressure transducer between two line valves. An alarm should be installed to monitor the PRS. For context, the HTM says a pressure of 400 kPa is required for medical air to drive ventilators and for other respiratory applications.
In Ultra Controlo plants
The ULTRAAR ME datasheet (2026) lists a pressure reduction and sterile filtration system fitted twice in the plant, with duplex pressure reducers each adjustable from 3 to 10 bar, non return reducers, an integrated pressure gauge and isolation valves for section switchover. This is a description of the datasheet; it is not compared here with the HTM paragraphs.
Sources
- NHS England, HTM 02-01 Medical gas pipeline systems, Part A (2026), paras 3.71 to 3.78 and 4.79
- ULTRAAR ME datasheet (2026), as published on the product page