Oxygen and PSA
Can a PSA plant produce 99.5% oxygen?
Can an on-site plant produce oxygen above 95%, such as 99% or 99.5%?
Short answer
A single-stage PSA plant does not produce 99% or 99.5% oxygen: NHS England's HTM 02-01 (2026) puts PSA at up to 95%, with the rest mainly argon. Two-stage adsorption plants, with a second stage designed to remove argon, make Oxygen 98, varying between 96% and 100%, and 99.5% oxygen comes from cryogenic distillation.
Three grades, three processes
| Grade | How it is made | Oxygen content | Monographs |
|---|---|---|---|
| Oxygen 93 | Adsorption from ambient air: single-stage plant (Ph. Eur.), PSA or VSA (International Pharmacopoeia), molecular sieve process (USP) | 90.0% to 96.0%, the rest argon and nitrogen | Ph. Eur. 2455; USP Oxygen 93 Percent; International Pharmacopoeia Oxygen 93% |
| Oxygen 98 | Two-stage adsorption, with a second stage designed to remove argon | Nominal 98.0%, varying between 96% and 100% (Ph. Eur.); at least 96.0% (International Pharmacopoeia) | Ph. Eur. 3098; International Pharmacopoeia Oxygen 98% |
| Oxygen 99.5% | Cryogenic distillation of air | At least 99.5% (Ph. Eur. 0417); the USP Oxygen monograph sets at least 99.0% | Ph. Eur. 0417; International Pharmacopoeia Oxygen 99.5%; USP Oxygen |
Why single-stage PSA stops below 99%
The zeolite in a PSA plant preferentially adsorbs nitrogen while letting oxygen pass through (PATH and CHAI, 2021). HTM 02-01 states that PSA can produce oxygen concentrations of up to 95%, that the remaining content is mainly argon with some nitrogen, and that the maximum achievable concentration is unlikely to exceed 97/98%. A Global Fund purity note (April 2024) states that PSA purity does not exceed 96% because of the limits of the technology. The European Pharmacopoeia also has monograph 3098, Oxygen (98 per cent), and EDQM explains that one development behind it is a second adsorption stage designed to remove argon.
What it means for a hospital
- Oxygen 93 is medicinal oxygen in its own right: the International Pharmacopoeia (2025) defines medicinal oxygen as Oxygen 93%, Oxygen 98% or Oxygen 99.5%, and a 2017 health technology assessment by IETSI, part of Peru's EsSalud, found no pharmacopoeia or clinical guideline expressing a preference between 93% and 99% oxygen.
- Two-stage plants: EDQM noted in April 2020 that two-stage PSA plants producing a nominal 98.0% were now available, and an INFARMED circular of 29 October 2024 says 98% oxygen generators are in strong technological development, with certification processes started.
- Higher purity costs flow: the Global Fund note gives the example of equipment producing 20 Nm³/h at 93% (±3%) that would produce 18 Nm³/h if set to 95% (±1%).
- Mixed supplies: if the pipeline also receives oxygen from liquid or cylinders, ISO 7396-1:2016 states that the concentration can vary between 90% and above 99%. See mixing Oxygen 93 and 99% oxygen.
ULTRAOX SC and ST plants deliver oxygen at 93% ± 3%, according to their datasheets. See also what Oxygen 98 is and why PSA cannot reach 100% oxygen.
More questions
What is the rest of the gas in Oxygen 93?
Mainly argon, with some nitrogen, according to HTM 02-01; the European and US pharmacopoeias give argon and nitrogen.
Does the USP have a 99.5% oxygen grade?
The USP Oxygen monograph requires at least 99.0% oxygen, while European Pharmacopoeia monograph 0417 requires at least 99.5%.
Sources
- NHS England, HTM 02-01 Part A (2026), paragraph 6.111
- EDQM, monograph history, Oxygen (98 per cent) 3098, with the single-stage range of 2455
- EDQM, oxygen monographs 0417, 2455 and 3098 (news)
- The International Pharmacopoeia, 13th edition (2025), Medicinal oxygen
- USP, Oxygen 93 Percent
- USP, Oxygen
- Global Fund / Build Health International, Briefing Note: PSA Plant Oxygen Purity (3 April 2024)
- PATH and CHAI, Oxygen Generation and Storage: Pressure/Vacuum Swing Adsorption Plant (July 2021)
- INFARMED, Circular Informativa N.º 092/CD/100.20.200 (29 October 2024)
- ISO 7396-1:2016, scope (iso.org)
- IETSI-EsSalud, Dictamen Preliminar N° 029-SDEPFyOTS-DETS-IETSI-2017, Uso de oxígeno medicinal al 93 por ciento (June 2017)
- ULTRAOX SC datasheet, 2026 edition (oxygen purity)
- ULTRAOX ST datasheet, 2026 edition (oxygen purity)