Medical gas library

Oxygen and PSA

Can Oxygen 93 and 99.5% oxygen share the same pipeline?

Can Oxygen 93 from a PSA plant and 99.5% oxygen from liquid or cylinders be connected to the same pipeline?

Short answer

Technically yes: ISO 7396-1:2016 covers supply systems that combine Oxygen 93 sources with oxygen sources, in which case the concentration in the pipeline can vary between 90% and above 99%. Whether it is allowed depends on national rules, and some, such as Portugal's ACSS specification, recommend a separate or dedicated network for Oxygen 93.

Request a quote

What the standard and the pharmacopoeia say

The scope of ISO 7396-1:2016 describes three kinds of oxygen supply system. Where all sources deliver Oxygen 93, the concentration may vary between 90% and 96%. Where all sources deliver oxygen, it is above 99%. Where Oxygen 93 and oxygen sources are combined, the gas in the pipeline can vary between 90% and above 99%. A new edition of ISO 7396-1 was under publication on 22 October 2026, so the edition in force should be checked before a design is fixed.

The International Pharmacopoeia (13th edition, 2025) defines medicinal oxygen as Oxygen 93%, Oxygen 98% or Oxygen 99.5%. It states that mixtures of these qualities may be used clinically, but that the requirements of its monograph do not apply to any such mixture. During the revision, an open letter from the Every Breath Counts coalition, written on behalf of members including the World Federation of Societies of Anaesthesiologists (WFSA) and posted by WFSA on 18 March 2022, proposed wording that oxygen from 93% and 99.5% sources of defined quality can be safely mixed and given to patients.

Where national guidance differs

  • Portugal: the ACSS specification ET 03/2006 (revised June 2024) recommends a separate or dedicated distribution network for Oxygen 93, for traceability, and requires that, besides the three Oxygen 93 sources, a source of medicinal oxygen is always provided and available whenever needed.
  • England: HTM 02-01 (2026) says an emergency reserve manifold working with a PSA should supply the same oxygen concentration as the PSA, and notes that cylinders from a gas supplier are above 99%.
  • Responsibility: EIGA Doc 195, adopted as AIGA 113/20, places the quality and safety of Oxygen 93 given to patients with a person nominated by the healthcare facility, normally the head pharmacist.

ULTRAOX SC and ST plants deliver oxygen at 93% ± 3%, inside the Oxygen 93 range. When such a plant is connected to a network that already has liquid or cylinder oxygen, the hospital, its pharmacist and the health authority decide which of these approaches applies. See also Oxygen 93 and what backup to keep with a PSA plant.

More questions

Is Oxygen 93 a medicinal grade?

Yes. The International Pharmacopoeia (2025), the European Pharmacopoeia (monograph 2455) and the US Pharmacopeia (Oxygen 93 Percent) define it, with 90.0% to 96.0% oxygen.

What oxygen concentration does a mixed supply system give?

ISO 7396-1:2016 states that a supply system combining Oxygen 93 and oxygen sources can vary between 90% and above 99%.

Sources

Ultra Controlo figures come from its technical datasheets. Third-party facts were read at the source on the date shown.

Reviewed: · Ultra Controlo engineering · Markdown version