Vacuum and AGSS
Can portable suction replace central vacuum in small hospitals?
Can small hospitals rely on portable suction units instead of a central medical vacuum system?
Short answer
Under HTM 02-01 (2026), the NHS England guidance, mobile electric suction units are not appropriate for the main vacuum supply, because of the power consumption and efficiency of the individual pumps; where vacuum is used regularly a pipeline should be installed, with mobile units kept for emergencies or where a pipeline would be used infrequently.
What HTM 02-01 (2026 edition) says about mobile and portable suction:
- Electric suction may not be as efficient as pipeline suction in areas of regular use; where vacuum will be regularly used, a pipeline system should be installed, and mobile electric vacuum (MEV) units should be provided as an emergency supply or where the pipeline system is likely to be used infrequently (2.56).
- Mobile electric suction units are not appropriate for the main supply, because of the power consumption and efficiency of the individual pumps (10.11).
- For non-acute healthcare facilities with low vacuum demand, such as hospices and satellite dialysis units, the plant should reflect the expected usage profile, and a duplex configuration may be considered, provided that system resilience and continuity of supply are maintained; the level of resilience should be justified through risk assessment and agreed with the Authorised Person (MGPS) and the Authorising Engineer (MGPS) (10.10).
- In the example central vacuum systems of Table 21, the primary and secondary supplies are pumps of a triplex or quadruplex set and the tertiary supply is portable suction equipment with battery backup; vacuum systems may have battery or injector-driven suction as a tertiary source (2.37).
If mobile units are used
Where mobile electric suction units are proposed, HTM 02-01 asks for the Medical Gas Safety Group to be consulted and for the design to cover staff training, equipment maintenance, resilience of supply with emergency provision and backup devices, the staff resources to allocate and manage the devices, storage, charging areas with HTM 05 considerations for lithium-ion batteries, areas for testing and decontamination, critical spares, life-cycle costing, and pharmacy and clinical team considerations (10.12). Ejector suction units and other alternatives need the same considerations, plus the increased demand on, and impact on, the driving gas (10.13).
Alongside piped vacuum, MEV provision should be set by risk assessment: typically, one unit may be provided on the resuscitation trolley together with at least one MEV per 15 outlets in each non-critical ward or department with piped vacuum, and in critical care, as a general rule, one unit may be provided for every five patients (2.57, 2.58). Electrically powered medical and surgical suction equipment, including units for use in hospitals, for field use and for transport, is covered by ISO 10079-1:2022, which has an amendment of 2026.
Portugal
Portugal's ACSS ET 03/2006 (v.2024) asks for permanently connected backup supplies of oxygen, medical air and vacuum in the most critical services, operating theatres and intensive care, which start automatically if the central supply fails; the vacuum part is a compact plant of 25 to 40 m³/h installed close to the service (section 8).
ULTRAVAC
ULTRAVAC centralised medical vacuum systems are built with 1 to 12 vacuum pumps, with capacities per pump from 3 to 1,600 m³/h.
More questions
Can portable suction be the backup to a central vacuum plant?
Yes in HTM 02-01 (2026) terms: its example central vacuum systems use portable suction equipment with battery backup as the tertiary supply, and MEV units as an emergency supply.
What must be planned if a facility relies on mobile suction units?
HTM 02-01 (2026) asks for the Medical Gas Safety Group to be consulted and for training, maintenance, backup devices, storage, battery charging, decontamination, spares and life-cycle costs to be covered in the design.
Sources
- NHS England, HTM 02-01 (2026 edition) Part A, paras 2.37, 2.56 to 2.58, 10.10 to 10.13 and Table 21
- ISO 10079-1:2022, Medical suction equipment, Part 1: Electrically powered suction equipment (iso.org summary)
- ACSS ET 03/2006 v.2024, section 8 (backup supplies for critical services)
- ULTRAVAC datasheet, pp. 2 and 5
Ultra Controlo figures come from its technical datasheets. Third-party facts were read at the source on the date shown.