Do vacuum and AGSS pumps deliver more flow at 60 Hz?

Does a medical vacuum or anaesthetic gas scavenging pump deliver a different flow on a 60 Hz supply than on 50 Hz?

Short answer

Yes: in the ULTRAVAC and ULTRASEG datasheets every vacuum and AGSS pump model is listed with a higher capacity at 60 Hz than at 50 Hz, for example 3x60 instead of 3x50 m³/h for an ULTRAVAC 3.50/500 and 60 instead of 50 m³/h for an ULTRASEG E50.

Both datasheets print a 50 Hz and a 60 Hz capacity column side by side for each model, so the same model has two capacity figures. The ULTRASEG table also gives the motor power at each frequency; the ULTRAVAC table gives motor power at 50 Hz only.

ULTRASEG anaesthetic gas scavenging, per pump

ModelCapacity at 50 Hz (m³/h)Capacity at 60 Hz (m³/h)Motor at 50 Hz (kW)Motor at 60 Hz (kW)
H5050580,550,63
E5050600,20,23
E1001031200,40,5
H1701701952,22,55
E3003153762,22,55

ULTRAVAC medical vacuum, triplex plants

ModelCapacity at 50 Hz (m³/h)Capacity at 60 Hz (m³/h)Motor power at 50 Hz, three-phase (kW)
3.10/2003x103x123x0,37
3.25/5003x253x303x0,75
3.50/5003x503x603x1,25
3.100/10003x1103x1323x3,0
3.300/10003x3003x3603x7,5

Rows selected from the full tables in the ULTRASEG and ULTRAVAC datasheets, as printed. Ultra Controlo engineering confirms the configuration for each project.

Voltage and frequency in the Ultra Controlo datasheets

  • ULTRASEG: motor voltage 200 to 240 V Δ / 345 to 415 V Y at 50 Hz and 220 to 275 V Δ / 380 to 480 V Y at 60 Hz; the datasheet states that other voltages and frequencies are supplied according to the country regulations.
  • ULTRAVAC: the datasheet text gives motor power of 0.37 to 40 kW, 400 V, 50 Hz.
  • ULTRALOBO LPT oxygen boosters: 400 V/50 Hz, other on request.
  • ULTRAGEC 4 emergency cabinet: 230 V / 50 Hz.

For PSA oxygen plants, see does 50 Hz or 60 Hz matter for an oxygen plant. For the AGSS model in the first table, see ULTRASEG E50.

More questions

Does the ULTRAVAC datasheet give motor power at 60 Hz?

No. Its table gives motor power at 50 Hz only, for three-phase and single-phase motors.

Can ULTRASEG be supplied for a 60 Hz network?

The ULTRASEG datasheet lists 60 Hz capacities and motor voltages, and states that other voltages and frequencies are supplied according to the country regulations.

Sources

Ultra Controlo figures come from its technical datasheets. Third-party facts were read at the source on the date shown.

Reviewed: · Ultra Controlo engineering · Markdown version