How often should hospital medical air and vacuum plants be serviced?
Short answer
HTM 02-01 Part B (2026 edition), the NHS England guidance, gives minimum recommended frequencies for plant tasks, with weekly checks of alarms, hours run, oil and drains, quarterly and annual checklists, and gas quality tests at least quarterly, and says the actual frequency should be set from the plant manuals.
HTM 02-01 Part B (2026 edition) is the operational management part of the NHS England guidance. Its maintenance section gives "the minimum tasks at the minimum recommended frequency", including details of daily and weekly tests, and says the daily and weekly tasks are usually carried out by the healthcare organisation's estates team, although it may ask the contractor to do some or all of them as an additional contract.
Weekly checks
For medical gas plant, the weekly tasks include checking the plant control panels for alarm conditions, recording hours run for each compressor or pump, a visual check for security and oil leakage, checking the oil level, manually opening the drains in turn to test the automatic drains, and checking the dryer control panels. For vacuum plant, they include checking pump motor and control panels, recording hours run, checking the oil level, checking the bacteria filter and exhaust drainage flasks for liquid, recording vacuum cut-in and cut-out levels, and changing over duty and standby pumps.
Quarterly and annual work
HTM 02-01 says the quarterly and annual procedures and checklists in Part B may be used with manufacturers' data to prepare maintenance schedules. It also says the quality of gas from PSA and medical air compressors should be tested "at least quarterly" using the Part A procedures. Filters on the pipeline system should be changed at the intervals the manufacturer recommends, more often if a filter becomes wet or its pressure drop exceeds the supplier's specification. For vacuum plant, Part B adds that bacteria filter elements are usually replaced annually or after a specified number of hours, whichever comes first.
The actual frequency
HTM 02-01 says the actual frequency should be established from the equipment and plant manuals together with the guidance, and that records, risk assessments and plant history logs may justify changing it. Its example is raising inspection frequency from quarterly to monthly, or even weekly.
Portugal
ACSS ET 03/2006 v.2024, the Portuguese hospital specification for medical gases and vacuum, refers its maintenance aspects to Subsection 2.13 of the ACSS recommendations and technical specifications for hospital buildings, which was not opened for this page, so no Portuguese service interval is given here. For the plants themselves, see What maintenance does a medical air plant need? and What maintenance does a medical vacuum plant need?.
More questions
Who normally does the weekly checks on medical gas plant?
HTM 02-01 says daily and weekly tasks are usually carried out by the healthcare organisation's estates team, though a contractor may be asked to do some or all of them.