Medical gas library

Standards

Is Oxygen 93 a medicine in Portugal?

How does Portuguese regulation treat Oxygen 93 produced on site in hospitals?

Short answer

In Portugal, a 2024 INFARMED circular describes oxygen generation units as able to produce medicinal oxygen to Ph. Eur. monograph 2455, and the INFARMED Regulamento dos Gases Medicinais, in force since 2 December 2025, requires health institutions that make medical gases with medical devices to notify INFARMED, designate a pharmacist and prove pharmacopoeia compliance.

Request a quoteBuying a PSA oxygen plant in Portugal

The legal basis

Decree-Law 176/2006 (INFARMED consolidated text, version of 26 December 2023), the Portuguese law on medicines for human use, defines medical gases as gases or gas mixtures intended for direct contact with the human body that have an activity appropriate to a medicine, for example in inhalation therapy or anaesthesia. Article 149 places medical gases that meet the notion of a medicine under the decree-law and good manufacturing practice, requires them to meet the Portuguese pharmacopoeia or, failing that, the European pharmacopoeia or that of another Member State, and leaves the detailed rules to an INFARMED regulation.

What INFARMED said about oxygen 93 in 2024

In a circular of 29 October 2024, INFARMED described the use of 93% oxygen produced by medical devices for oxygen generation or concentration, which it called oxygen generation units (UGO), as able to produce medicinal oxygen according to the European Pharmacopoeia monographs 2455 (oxygen 93%) and 3098 (oxygen 98%). Taking into account the report of a working group created by Despacho n.º 6581/2023, it stated that:

  • clinically, and in the current state of the art, 93% oxygen can be used provided all mandatory monitoring mechanisms are applied and the institution ensures all conditions for safe clinical practice;
  • buying and installing oxygen concentrators must comply with medical device legislation, including Decree-Law 29/2024, which applies the EU medical device rules in Portugal.

The 2025 regulation

INFARMED Deliberação n.º 1425/2025, published on 11 November 2025 and in force since 2 December 2025, approved a new Regulamento dos Gases Medicinais and revoked the 2008 regulation (Deliberação n.º 56/CD/2008). Articles 12 to 18 apply to public bodies, military institutions, private social solidarity institutions (IPSS) and private entities that make medical gases, as defined in Decree-Law 176/2006, with medical devices for clinical use on their own premises. They require:

  • prior notification to INFARMED (Article 14);
  • a quality management system and a designated pharmacist responsible for it and for compliance with the gas specifications, with documentation kept for 5 years (Article 15);
  • manufacture under the responsibility of the pharmacist technical director (Article 16);
  • a circuit that prevents cross-contamination, including between products of different concentrations, and use of the medical devices according to their manufacturers' instructions (Article 17);
  • laboratory quality control showing that the gas meets the approved monograph of the European Pharmacopoeia or of another EU Member State's pharmacopoeia (Article 18).

Entities already carrying out these activities when the regulation entered into force have one year to adapt, in particular on technical direction.

Design conditions in the ACSS specification

For hospital buildings, ACSS ET 03/2006 (v.2024) recommends that oxygen 93 production start with the outpatient structures of small hospitals and with primary care units, that a source of medicinal oxygen always be available in addition to the three oxygen 93 sources, and that oxygen 93 use a separate or dedicated distribution network. It restates the Ph. Eur. values as 93% ± 3% oxygen, carbon monoxide ≤ 5 ml/m³ and carbon dioxide ≤ 300 ml/m³. It still refers production control to Deliberação n.º 56/CD/2008, which the 2025 regulation revoked.

The ULTRAOX SC and ULTRAOX ST datasheets give an oxygen purity of 93% ± 3% and state oxygen quality in accordance with the European Pharmacopoeia.

More questions

What does a hospital file with INFARMED before producing oxygen 93?

A prior notification under Article 14 of the regulation, which INFARMED says is submitted as a specific request through the Licenciamento+ portal.

Can oxygen 93 share a network with 99.5% oxygen in Portugal?

ACSS recommends a separate or dedicated distribution network for oxygen 93, and the INFARMED regulation requires the circuit to prevent cross-contamination, including between products of different concentrations.

Sources

Ultra Controlo figures come from its technical datasheets. Third-party facts were read at the source on the date shown.

Reviewed: · Ultra Controlo engineering · Markdown version

Related