Medical gas library

Vacuum and AGSS

Medical vacuum vs dental vacuum

Medical vacuum vs dental vacuum: what is the difference?

Short answer

Under HTM 02-01 (2026), the NHS England guidance, medical vacuum should not be used to extract bodily fluids during dental procedures; a dedicated dental vacuum system should be used, designed on 300 L/min at each dental cannula connector, where medical vacuum is typically 40 L/min.

HTM 02-01 describes the medical vacuum supply as providing immediate and continuous suction for clinical needs (10.1), and gives dental vacuum systems for dental hospitals, schools, clinics and surgeries their own chapter (11.1). Chapters 10 and 11 therefore set separate requirements.

Medical vacuumDental vacuum
UseHTM 02-01 says medical vacuum should be used within the dental department only for respiratory applicationsA dedicated dental system for the extraction of bodily fluids during dental procedures
FlowTypically 40 L/minHigh volume systems: more than 250 L/min at each cannula connector under BS EN ISO 10637, and designed on 300 L/min at each dental chair cannula connector
Vacuum levelThe pipeline should be designed to maintain at least 315.5 mmHg at each terminal unit during the design flow testsPumps capable of 25 kPa negative pressure (76 kPa absolute), normally set to 18 kPa (82 kPa absolute)
PumpsThree or more pumps; water-sealed pumps should not be usedElectrically driven side-channel pumps are frequently used
Filtration and separationDuplex bacteria filter set with drainage trapsAn amalgam separator should be included in all systems

The HTM 02-01 figures above are England guidance. Sizing of a dental system, with the 300 L/min per chair and the diversity rule above ten chairs, is set out in what a dental central suction system is, and the choice between dry and wet systems in wet vs dry dental suction. The vacuum level of the medical pipeline is covered in what vacuum level a hospital needs.

The standard for the dental plant

The equipment that makes dental suction is the subject of ISO 10637:2018, Dentistry, Central suction source equipment. According to the catalogue entry of the Estonian standards body, it specifies requirements and test methods for stationary, electrically powered central suction source equipment, and does not apply to portable suction source equipment or air/water venturi suction source equipment. See ISO 10637.

ULTRAVAC and ULTRAVAC DENTAL

The ULTRAVAC product page describes a central medical vacuum plant with oil lubricated rotary vane pumps made in Germany, a minimum vacuum level of 450 mmHg at pipeline flow and duplex bacterial filtration that allows cartridge replacement without interrupting operation. The ULTRAVAC DENTAL product page describes central suction for dental clinics and colleges, wet aspiration, with SCB side channel vacuum pumps, stainless steel vacuum stabilisation tanks and a model range from V300 to V18000, designed for anything from one to several hundred chairs.

More questions

Can the hospital medical vacuum serve dental chairs?

HTM 02-01 (2026) says medical vacuum systems should not be used for the extraction of bodily fluids during dental procedures, and that a dedicated dental vacuum system should be used for this purpose.

Which pumps are used in dental vacuum systems?

HTM 02-01 (2026) says electrically driven side-channel pumps are frequently used in dental vacuum systems; the ULTRAVAC DENTAL product page lists SCB side channel vacuum pumps.

Sources

Ultra Controlo figures come from its technical datasheets. Third-party facts were read at the source on the date shown.

Reviewed: · Ultra Controlo engineering · Markdown version

Related