Medical air
Pressure dew point vs atmospheric dew point
Short answer
The 2016 US DOE sourcebook defines pressure dew point as the temperature at which water begins to condense out of air at a given pressure, and says it differs from the dew point at atmospheric conditions; HTM 02-01 (2026), the NHS England guidance, states medical air dryness as an atmospheric pressure dew point.
A dew point in compressed air depends on the pressure of the air. The 2016 US DOE sourcebook explains that when air is compressed it can no longer contain all of the moisture possible at atmospheric conditions, so some of the moisture drops out as liquid condensate, and that the result is a difference between the dew point at atmospheric conditions and the dew point at higher pressures. Its glossary defines pressure dew point as, for a given pressure, the temperature at which water will begin to condense out of air.
Side by side
| Pressure dew point | Atmospheric dew point | |
|---|---|---|
| What it describes | The temperature at which water begins to condense out of the air at a given pressure (DOE sourcebook glossary) | The dew point at atmospheric conditions, which the sourcebook says differs from the dew point at higher pressures |
| Where the sources use it | ULTRADRY datasheet: pressure dew point range of −40 °C to −70 °C. ACSS ET 08/2010 (V.2025), the Portuguese specification for technical (non-medical) compressed air in hospital buildings: humidity class 4 as a PDP of up to +3 °C at 20 °C average temperature and 0.7 MPa | HTM 02-01 (2026): the dryer control unit hygrometers are set to −46 °C atmospheric dew point, and terminal units are tested for water vapour not above 67 vpm, equivalent to an atmospheric pressure dew point of approximately −46 °C |
| Equivalence stated by the source | ACSS ET 08/2010 (V.2025) gives an atmospheric dew point of up to −21 °C as equivalent to its PDP of up to +3 °C at 20 °C and 0.7 MPa | HTM 02-01 (2026) gives 67 vpm, or 0.05 mg/L, as equivalent to approximately −46 °C |
Reading a specification
The two equivalences in the table are each given by their own document for their own conditions. The DOE sourcebook adds that drying compressed air beyond the required pressure dew point results in unnecessary energy and costs, so the pressure at which a dew point is stated is part of the requirement.
ISO 7183:2007, the standard for compressed-air dryer specifications and testing, lists pressure dew point among the dryer parameters for which it identifies test methods, according to its iso.org abstract. See ISO 7183.
More questions
Is the minus 46 °C in HTM 02-01 a pressure dew point?
HTM 02-01 (2026) gives it as an atmospheric pressure dew point of approximately −46 °C, equivalent to 67 vpm of water vapour, for testing terminal units, and sets the dryer control unit hygrometers to −46 °C atmospheric dew point.
What does ACSS ET 08/2010 say a pressure dew point of up to +3 °C is equivalent to?
ACSS ET 08/2010 (V.2025) gives it as equivalent to an atmospheric dew point of up to −21 °C, for its humidity class 4 at 20 °C average temperature and 0.7 MPa.
Sources
- US DOE and Compressed Air Challenge, Improving Compressed Air System Performance, 3rd edition (2016): Introduction, p. 12 (PDF p. 17); Glossary (PDF p. 92)
- NHS England, HTM 02-01 Part A (August 2026 edition): 7.87 and 20.70
- ACSS ET 08/2010 V.2025, 4.1.1 (PDF p. 14)
- ISO 7183:2007, Compressed-air dryers, Specifications and testing (iso.org)
- ULTRADRY datasheet, p. 3
Ultra Controlo figures come from its technical datasheets. Third-party facts were read at the source on the date shown.