Oxygen and PSA
Adiabatic compression in oxygen systems
Under AIGA 113/20, adiabatic compression is one of three causes of the temperature increase that can ignite materials when oxygen 93 is compressed, with mechanical friction and particle impingement; HTM 02-01 (2026) says cylinder valves should be opened slowly because ignition may occur as a result of adiabatic compression.
AIGA 113/20 lists, among the additional hazards of compressing oxygen 93, the ignition of materials due to a temperature increase caused by mechanical friction due to malfunction of the compressor, particle impingement, which gives a localized high temperature, and adiabatic compression. It says the main consequences of such ignition can be a loss of containment and projection of molten metal at high pressure, and a release of a toxic combustion by-product. To mitigate these hazards it asks for monitoring of the compressor with automatic shutdown and alarms, a dedicated enclosure, correct selection of materials, and carbon monoxide and carbon dioxide analysis downstream.
HTM 02-01 (2026) Part B says cylinder valves should be opened slowly to prevent rapid pressurisation of the system, and that ignition may occur as a result of adiabatic compression, particularly in the presence of contaminants such as oil, grease or hand-cream residues. It also lists high-flow oxygen and rapid depressurisation, which can generate heat through adiabatic compression, among the ignition sources. WHO's Foundations of medical oxygen systems (2023) asks for oxygen cylinder valves to be opened smoothly to avoid (adiabatic) compression and heat generation and the associated fire risks.
Sources
- AIGA 113/20 (adopted from EIGA Doc 195), On site generation of oxygen 93% for medicinal use, section 6.13
- NHS England, HTM 02-01 (2026) Part B, paragraphs 9.164 and 10.33
- WHO, Foundations of medical oxygen systems (17 February 2023), section 3.6.1