Standards
HTM 02-01: medical gas pipeline systems (NHS England)
HTM 02-01 is NHS England's guidance for medical gas pipeline systems in healthcare premises; the current edition, published on 19 August 2026 in two parts (Part A design, installation, validation and verification; Part B operational management), supersedes all previous versions and HTM 2022.
Scope
HTM 02-01 covers medical gas pipeline systems (MGPS) in healthcare premises. Part A deals with design, installation, validation and verification and runs to 262 pages; Part B deals with operational management and runs to 197 pages. It treats medical gases as medicines, which must comply with the Human Medicines Regulations 2012 and the relevant British Pharmacopoeia monographs.
What changed in the 2026 edition
- The core engineering principles of the previous edition remain; the change is towards risk-based design and assurance.
- A Medical Gas Safety Group (MGSG) becomes part of the organisation's governance.
- A technical file for the MGPS is required and has to be updated with every modification or extension.
- It reports the recommendation of anaesthetic organisations that piped nitrous oxide should no longer be considered in modern anaesthetic practice.
Key technical points
- Sources of supply: following BS EN ISO 7396-1, every medical gas supply should have three sources, identified as primary, secondary and tertiary (Part A, 2.23).
- Pressures: medical air is treated as a 400 kPa service; surgical air should give at least 700 kPa at the terminal unit at a flow of 350 L/min or 100 L/min (Part A, 4.48).
- PSA oxygen: in the English context, PSA should only be considered where geographical or environmental constraints prevent liquid oxygen or cylinder supply (Part A, 6.108). The guidance states that PSA can produce up to 95% oxygen, the rest mainly argon, and that the emergency reserve manifold is typically set to activate below 94% (Part A, 6.111).
- Copper pipe: pipes are to be cleaned and degreased for oxygen service in accordance with BS EN 13348.
Points to watch
- Specifications that still cite the 2006 edition of HTM 02-01 or HTM 2022 are out of date.
- Part B still cites ISO 10083 (with BS 7634) for oxygen concentrator supply systems, although ISO withdrew ISO 10083 in February 2016 and lists ISO 7396-1:2016 as the document that revised it.
- Outside England, the Portuguese ACSS ET 03/2006 (v.2024) still lists HTM 2022 among the documents accepted for sizing distribution networks.
Related standards
HTM 02-01 builds on ISO 7396-1, the international pipeline standard, and refers to EN 13348 for copper tube. WHO names ISO 7396-1, HTM 02-01 and NFPA 99 as the three reference standards widely used for MGPS design.
More questions
Is the 2006 edition of HTM 02-01 still current?
No. The 2026 edition, published on 19 August 2026, supersedes all previous versions and HTM 2022.
Does HTM 02-01 recommend PSA oxygen plants?
No. For England, it says PSA should only be considered where geographical or environmental constraints prevent liquid oxygen or cylinder supply.
Sources
- NHS England, Health Technical Memorandum 02-01: Medical gas pipeline systems (publication page)
- HTM 02-01 Part A: Design, installation, validation and verification (2026)
- HTM 02-01 Part B: Operational management (2026)
- ISO 10083:2006 (withdrawn), iso.org
- WHO, Foundations of medical oxygen systems (2023)
- ACSS ET 03/2006 v.2024, Gases medicinais e aspiração
Ultra Controlo figures come from its technical datasheets. Third-party facts were read at the source on the date shown.
Related
- StandardsISO 7396-1: pipelines for compressed medical gases and vacuum
- StandardsEN 13348: copper tubes for medical gases and vacuum
- StandardsNFPA 99: Health Care Facilities Code for medical gases
- GlossaryHTM 02
- AnswersWhat changed in the 2026 edition of HTM 02-01?
- ComparisonsISO 7396-1 vs HTM 02-01 vs NFPA 99: how do they differ?