Medical air

What does a complete compressed air treatment chain look like?

What does a complete compressed air treatment chain look like, from compressor to point of use?

Short answer

The Compressed Air Challenge Fact Sheet #11 (May 2026) counts air treatment equipment, such as dryers, filters, receivers and condensate separators, as one of five compressed air subsystems and says drying, filtration and distribution should keep the pressure drop from compressor to points of use much less than 10% of discharge pressure.

The fact sheet says air treatment equipment must provide for both contaminant removal and preparation of the air for equipment use, and that drying should only be performed to the degree the equipment and end use need. The sources describe these stages, each with the position its source gives, where it gives one:

  • Aftercooler and moisture separator. The DOE sourcebook (2016) says aftercoolers, installed after the final stage of compression, condense, separate, collect and drain water vapour as they cool the air, and a separator is generally installed after each intercooler or aftercooler.
  • Wet receiver. CAC Fact Sheet #11 says the receiver is located before the dryer in most systems, and that a best practice is a wet receiver before the dryer and a dry receiver directly after it.
  • Pre-filtration. Gardner Denver says a water separator installed before a coalescing filter protects it against bulk liquid contamination, and CAC Fact Sheet #11 recommends a coalescing filter before a desiccant dryer to prevent fouling of the desiccant bed.
  • Dryer. A refrigerant or desiccant dryer; CAC Fact Sheet #11 says drying should only be performed to the degree the equipment and end use need.
  • Dry receiver and after-filtration. CAC Fact Sheet #11 puts the dry receiver directly after the dryer and recommends a particulate filter after a desiccant dryer to remove desiccant fines. For an activated carbon stage against oil vapour, Gardner Denver says its grade V carbon filter should be preceded by its grade H filter, and the ULTRAK datasheet requires a coalescing filter upstream and recommends a 1 μm dust filter downstream.
  • Condensate treatment. CAC Fact Sheet #11 says condensate can no longer be discharged to sewer lines without treatment to remove contaminants such as entrained lubricants, except condensate from some lubricant-free systems; condensate/lubricant separators work by settling tanks and/or permeable membranes.
  • Distribution and point of use. The distribution subsystem includes drops to specific usage points, pressure regulators and lubricators, additional filters and traps, and supplementary air treatment equipment; CAC Fact Sheet #5 (May 2026) says point-of-use filters, regulators and lubricators give a tool a clean, lubricated supply of air at the proper pressure.

Pressure drop budget

CAC Fact Sheet #11 says the complete drying, filtration and distribution system should be sized and arranged so that the total pressure drop from the air compressor to the points of use is much less than 10% of the compressor discharge pressure; Fact Sheet #4 (May 2026) says a properly designed system should have a pressure loss of much less than 5% of the compressor discharge pressure from the receiver tank output to the point of use. Filtration only to the level each application requires minimises pressure drop and energy consumption.

The ULTRASEC datasheet describes a refrigeration dryer, the ULTRADRY datasheet an adsorption dryer with a pressure dew point range of −40 °C to −70 °C, and the ULTRAK datasheet a tower that separates oil vapours from compressed air. Ultra Controlo supplies these three and distributes and services Gardner Denver in Portugal, whose range includes compressed air filters.

More questions

Should the receiver go before or after the dryer?

CAC Fact Sheet #11 (May 2026) says most systems place it before the dryer and calls a wet receiver before the dryer and a dry receiver directly after it a best practice.

How much pressure drop can the treatment chain take?

CAC Fact Sheet #11 (May 2026) says the total pressure drop from the compressor to the points of use should be much less than 10% of the compressor discharge pressure.

Sources