Industry
How are several air compressors controlled together?
How are several air compressors controlled together on one network?
Short answer
Compressed Air Challenge Fact Sheet #6 (May 2026) describes two ways to control several compressors on one header: a single master sequencer that makes all operating decisions, or multi-master network controls in which linked compressor controllers share information and one acts as leader.
Fact Sheet #6 says compressor systems typically have multiple compressors delivering air to a common plant air header, with a combined capacity sized, at a minimum, to meet the maximum plant air demand. System controls are almost always needed to reduce the output of individual compressors when demand is lower. The objective of any control strategy is to shut off unneeded compressors or delay bringing on additional ones until needed, and all units that are on should run at full load, except one unit for trimming.
Why the pressure band matters
Systems are usually designed to operate within a fixed pressure range. The difference between the pressure at which output is reduced and the lower pressure at which it is increased again is the control range, which can be anywhere from 2 to 20 psi depending on demand. Every 2 psi of pressure difference is equal to about a 1% change in energy consumption, so tighter control allows a lower pressure set point. Lowering average header pressure needs caution, because large, sudden changes in demand can drop pressure below the minimum, and careful matching of controls and storage avoids this.
System controls for several compressors
| Control | What Fact Sheet #6 says |
|---|---|
| Single master (sequencing) controls | Sequencers regulate the system by staging individual compressor capacity to meet demand, taking it on and off line in response to monitored system pressure. They are single master units because all operating decisions are made and directed from the master unit. |
| Multi-master (network) controls | Each compressor controller has system control capability. The controllers are networked together and share all operating information and status, and one of them is designated the leader. Decisions on changing demand can be made more quickly and accurately. |
| Flow controllers | A flow controller does not directly control a compressor and is generally not part of the compressor package. It separates the supply side from the demand side, so compressors run near their optimum pressures while demand-side pressure is reduced. Storage sized for anticipated demand fluctuations is an essential part of this strategy. |
Controls of the individual compressor
The fact sheet also describes the controls inside each compressor. Start/stop is the simplest, and load/unload keeps the motor running while unloading the compressor; in most cases an unloaded rotary screw compressor consumes 15 to 35% of full-load horsepower while delivering no useful work. Variable frequency drives are widely accepted in compressor applications. See variable speed or fixed speed compressors.
Fact Sheet #1 adds that for plants with wide variations in air demand, multiple compressors with sequencing controls may provide more economical operation. See how an industrial air compressor is sized.
ULTRASCREW DS VSD
The ULTRASCREW DS VSD product page says several compressors can run as a group without an external master controller. It lists an LED display with integrated driver and controller, Modbus TCP and dual PID control of pressure and temperature at the same time. The page does not say which of the control types above the group function uses. See ULTRASCREW DS VSD.
More questions
What is a compressor sequencer?
According to Fact Sheet #6, a sequencer regulates a compressor system by sequencing or staging individual compressor capacity to meet demand, and it is a single master control unit because all compressor operating decisions are made and directed from it.
Can compressors run as a group without an external controller?
The ULTRASCREW DS VSD product page says several compressors can run as a group without an external master controller.
Sources
- Compressed Air Challenge, Compressed Air Systems Fact Sheet #6: Compressed Air System Controls (May 2026, Rev. 1)
- Compressed Air Challenge, Compressed Air Systems Fact Sheet #1: Assessing Compressed Air Needs (May 2026, Rev. 1)
- ULTRASCREW DS VSD product page, ultracontrolo.com (checked 18 November 2026)