Ultra Controlo Medical gas library

Medical air

How many compressors does a medical air plant need?

How many compressors and sources of supply does a medical air plant need?

Short answer

Under HTM 02-01 (2026), a medical air plant has at least two compressors with total capacity covering 100% of design flow, inside a supply of three sources: in a triplex plant two compressors are primary, the third is secondary and cylinder manifolds are tertiary.

ISO 7396-1 deals with the rule that a medical gas supply system has at least three sources of supply; ISO 7396-3 refers to it for that rule. HTM 02-01 (2026), following BS EN ISO 7396-1, says all medical gas supplies should have three sources, called primary, secondary and tertiary. In the HTM examples for medical air compressor plants, the compressors provide the primary and secondary supply.

Compressor sizing in HTM 02-01

The HTM asks for at least two compressors, and more may be added as long as the total capacity provides 100% of the system design flow. Its Table 16 sizes each compressor by configuration:

Configuration (medical air or combined plant)Each compressor sized at
Duplex (medical air)100% of design flow
Triplex50% of design flow
Quadruplex33% of design flow
Sextuplet20% of design flow
Octuplet15% of design flow

Receivers should have a minimum water capacity of 50% of the compressor output in one minute. VSD compressors are sized individually for the configuration, and where a VSD compressor provides the primary control of demand it should be sized to no more than 80% of the required flow rate.

Primary, secondary and tertiary sources

HTM 02-01 Table 17 gives two examples. In a triplex plant, two compressors are the primary supply, the third compressor is the secondary supply, and automatic manifolds with locally based ready-to-use cylinders are the tertiary supply. In a quadruplex plant, three compressors are primary, one is secondary, and manifolds and cylinders are tertiary. National rules can differ from the NHS England guidance, so the specification that applies to the project should be checked.

ULTRAAR plants

The ULTRAAR SC, ESW and ME datasheets give a basic configuration of one, two, three or more compressors. ULTRAAR ESW plants are designed with 1 to 8 compressors, and every model in the ULTRAAR ME table is a three-compressor set, such as the 3.15/500D with three compressors of 14.4 m³/h at 10 bar. ULTRAAR SC and ESW receivers are prepared to receive an additional emergency compressor.

More questions

Does the last source have to be a compressor?

No. In HTM 02-01 Table 17, automatic cylinder manifolds and locally based ready-to-use cylinders form the tertiary supply behind the compressors.

Can medical and surgical air share one plant?

Yes. HTM 02-01 recommends a single combined plant for medical and surgical air, and says a dual-purpose plant with VSDs should be specified as the most sustainable and efficient solution.

Sources

Ultra Controlo figures come from its technical datasheets. Third-party facts were read at the source on the date shown.

Reviewed: · Ultra Controlo engineering · Markdown version