Medical air
What is the reserve supply for a medical air system?
What reserve supply does a medical air system need if the compressors fail?
Short answer
A medical air system is built with three sources of supply, so that when the compressors fail a spare compressor or an automatic manifold of medical air cylinders takes over; NHS England guidance adds locally based ready-to-use cylinders, and Portuguese guidance a cylinder reserve in theatres and intensive care.
ISO 7396-1, the international standard for medical gas pipeline systems, requires a supply system with at least three sources of supply; ISO 7396-3 leaves that rule to Part 1. National guidance uses different names for them. HTM 02-01 in England calls them primary, secondary and tertiary, and the Portuguese ACSS ET 03/2006 calls them primary, secondary and reserve. In a compressor plant the compressors are the primary source, and the question is what takes over when they stop.
What the NHS England guidance specifies
HTM 02-01 (2026) says medical compressed air can be obtained from compressor systems and cylinders, and backs the compressors with automatic cylinder manifolds. Its examples include:
- Triplex compressor plant: two compressors as primary, the third compressor as secondary, and automatic manifolds plus locally based ready-to-use cylinders as tertiary.
- Combined medical and surgical air plant: two automatic manifolds as secondary, one for each service, which come online if the plant fails and hold enough cylinders for 4 hours of supply at average use; tertiary supply from automatic manifolds and locally based ready-to-use cylinders.
- Where the compressors could draw in smoke during a fire: an automatic shutdown linked to local smoke detectors, with the automatic emergency manifold sited well away from the fire-risk area and coming online automatically.
What the Portuguese specification asks for
ACSS ET 03/2006 (revised in June 2024) asks for three automatically operating compressor units, each rated at 100% of the nominal flow, and an emergency set of medical air cylinders able to supply the hospital for 24 hours. It also asks for permanently connected reserve systems for oxygen, medical air and vacuum in operating theatres and intensive care units. For medical air, that reserve is a service cylinder and an emergency cylinder with automatic changeover, and it must start automatically if the central supply fails.
Points to check in a design
- The reserve contains medical air: ACSS specifies cylinders of medical compressed air for the emergency set.
- Changeover is automatic and alarmed: HTM 02-01 raises a cylinder reserve pressure fault when the duty bank falls below 50% of normal cylinder pressure.
- A non-return valve upstream of the emergency cylinder connection stops the reserve from backfeeding the compressor plant (HTM 02-01).
- Reserve duration depends on the guidance applied: 4 hours at average use for the HTM manifold examples, 24 hours for the ACSS emergency set.
In Ultra Controlo plants, ULTRAAR SC and ULTRAAR ESW are configured with one, two, three or more oil-less compressors, and their receivers are prepared to receive an additional emergency compressor. For critical areas, the ULTRAGEC emergency cabinet holds B50 cylinders of oxygen and medical air and connects to the secondary network upstream of the area, so that supply continues if the network feeding it fails.
More questions
How long should the medical air reserve last?
HTM 02-01 sizes the automatic manifolds for 4 hours of supply at average use; ACSS ET 03/2006 asks for an emergency set of medical air cylinders that covers 24 hours of hospital operation.
Is a spare compressor enough as a reserve?
Not on its own. In HTM 02-01 a third compressor can be the secondary source, but automatic manifolds and ready-to-use cylinders still form the tertiary supply.
Sources
- ISO 7396-3:2025 abstract (three sources of supply dealt with in ISO 7396-1)
- NHS England, HTM 02-01 Medical gas pipeline systems, Part A (2026), paras 2.23, 7.1, 7.11, 7.25, 7.59, 7.89, Tables 17 and 19
- ACSS, ET 03/2006 v.2024 Especificações técnicas para gases medicinais e aspiração em edifícios hospitalares, sections 4.6 and 8
- ULTRAAR SC datasheet, p. 2 and 3; ULTRAAR ESW datasheet, p. 3
- ULTRAGEC datasheet, p. 2 and 4
Ultra Controlo figures come from its technical datasheets. Third-party facts were read at the source on the date shown.
Related
- AnswersHow many compressors does a medical air plant need?
- AnswersWhat is a medical gas emergency cabinet?
- AnswersWhat is a medical gas pipeline system (MGPS)?
- AnswersCan medical air be used for autoclaves and other building equipment?
- AnswersDoes medical air need continuous quality monitoring?
- AnswersHow does a desiccant air dryer regenerate?