Medical air
After-cooler
An after-cooler is a heat exchanger that cools air discharged from a compressor, and HTM 02-01 (2026), the NHS England guidance, says after-coolers should be fitted to oil-lubricated medical air compressor systems.
The US Department of Energy compressed air sourcebook (third edition, 2016) defines an aftercooler as a heat exchanger used for cooling air discharged from a compressor. It says aftercoolers are installed after the final stage of compression to reduce the air temperature, and that as the air cools, water vapor condenses and is separated and drained from the system.
HTM 02-01 (2026) says that after-coolers and inter-coolers, where required or specified, should form part of the compressor subassembly. It says after-coolers will be air-cooled and may need ducting with forced ventilation to give an adequate supply of cooling air, and that plant siting should provide airflow for cooling of the compressed air by the after-coolers as well as for the compressor intake and the compressors.
Drains and alarms
HTM 02-01 asks for electrically operated automatic drainage traps on the after-coolers, receivers, separators and coalescing filters. Its list of indicators for each compressor includes an after-cooler temperature high condition. The condensate itself is a separate subject: see condensate drain and oil/water separator.
Sources
- NHS England, HTM 02-01 Medical gas pipeline systems, Part A (2026), paras 7.18, 7.44, 7.45, 7.56 and 7.91
- US Department of Energy, Improving Compressed Air System Performance: A Sourcebook for Industry (third edition, 2016), Aftercoolers and Glossary
Ultra Controlo figures come from its technical datasheets. Third-party facts were read at the source on the date shown.