Medical gas library

Medical air

Cyclone water separator

Under HTM 02-01 (2026), the NHS England guidance, an inline cyclone water separator is the separator it asks to be installed between each compressor and the receivers of a medical air plant, fitted with a timed solenoid drain valve.

The US Department of Energy compressed air sourcebook (third edition, 2016) describes moisture separators as devices that remove liquids entrained in the air, working through changes in direction and velocity, and possibly with impingement baffles. HTM 02-01 (2026) separately describes the first stage of its air treatment: compressed air is introduced at a low level and directed against the side wall of a vessel, and this impact removes larger water and oil particles.

The HTM also asks for electrically operated automatic drainage traps on separators, among other parts of the plant. The liquid that is drained is condensate; see condensate drain.

The ULTRAAR ME datasheet (2026) lists cyclonic liquid separation with auto drain in each of the two air treatment chains of the plant.

Sources

Ultra Controlo figures come from its technical datasheets. Third-party facts were read at the source on the date shown.

Reviewed: · Ultra Controlo engineering · Markdown version

Related