Hospital oxygen demand calculator, with the HTM 02-01 flows

NHS England's HTM 02-01 (2026) plans critical care at 60 L/min per bed space with high-flow ventilation, 10 L/min without, and operating suites at 50 L/min for the first operating room plus 10 L/min for each of the others. The calculator adds these flows to your ward figures and converts the total to m³/h.

Total oxygen demand 
Critical care, high-flow0
Critical care, no high-flow0
Operating suites0
In-patient beds0
Other areas0
ULTRAOX ST units that cover it

    Capacities as printed in the ULTRAOX ST datasheet (p. 5). Ultra Controlo engineering confirms the configuration for each project.

    Email this estimate to Ultra Controlo

    Opens your email program with the figures filled in. Nothing is sent until you press send.

    A planning estimate from the HTM 02-01 flows, not a design. HTM 02-01 states that pipeline flow cannot be predicted precisely.

    What the calculator adds

    AreaFlow usedSource
    Critical care with high-flow ventilation60 L/min per bed space, all bed spaces assumed occupied and using oxygenHTM 02-01 (2026)
    Critical care without high-flow ventilation10 L/min per bed spaceHTM 02-01 (2026)
    Operating suites50 L/min for the first operating room and 10 L/min for each of the othersHTM 02-01 (2026)
    In-patient beds using oxygenYour flow per bed; HTM 02-01 gives a typical flow of 6 L/min and a design flow of 10 L/min per terminal unitHTM 02-01 (2026), Table 2
    Other areasYour own figure in L/min

    The total in L/min is multiplied by 60 and divided by 1,000 to give m³/h, the conversion WHO used in its 2020 interim guidance, and multiplied by 24 for m³ per day.

    Matching an ULTRAOX ST unit

    The calculator then lists the smallest ULTRAOX ST models whose capacity per unit, as printed in the ULTRAOX ST datasheet (p. 5), covers the total. ULTRAOX ST models range from 3.10 to 165.3 Nm³/h per unit, supply oxygen at a purity of 93% ± 3%, and the plants are modular and can be expanded without replacing the concentrator. Ultra Controlo engineering confirms the configuration for each project.

    Why this is an estimate

    • Flow cannot be predicted precisely. HTM 02-01 states that pipeline flow cannot be predicted precisely, but gives guideline flows that have proved adequate in practice.
    • The plant uses some of its own oxygen. HTM 02-01 says PSA regeneration uses a proportion of the product gas, which should be taken into account when sizing the plant.
    • Several methods exist. WHO's Foundations of medical oxygen systems (2023) sizes plants from estimated demand, built from beds per type of ward, wall outlets per bed or historical consumption, and warns that counting 100% of the outlets in use at maximum flow can easily oversize the source.
    • Today's use is not the need. Open Critical Care warns that current consumption may grossly underestimate optimal consumption, because patients who lack access to oxygen today must also be counted.

    The button under the result opens an email to Ultra Controlo with your figures; see also what information is needed for an oxygen plant quote.

    More questions

    Does the calculator replace a design?

    No. HTM 02-01 states that pipeline flow cannot be predicted precisely, and that the oxygen a PSA plant uses for regeneration should be taken into account when sizing it; the result is a planning figure to discuss with an engineer.

    What flow should I enter for ward beds?

    HTM 02-01 gives in-patient accommodation a typical flow of 6 L/min and a design flow of 10 L/min per terminal unit. WHO (2023) notes that average flow rates from clinical guidelines may not represent real practice in the facility.

    Is 60 L/min per critical care bed always needed?

    No. HTM 02-01 (2026) reduces it to 10 L/min per bed space where there is no requirement for high-flow ventilation.