Short answer

The Compressed Air Challenge Fact Sheet #11 (May 2026) assigns lubricant and moisture to coalescing filters and vaporous contaminants to adsorbent filters; in the ULTRAK activated carbon tower, for example, oil vapours are separated from the compressed air by dry separation, with a coalescing filter required upstream.

ISO 12500, the series of test methods for compressed air filters, treats oil in two separate parts. Part 1 (2007) covers coalescing filters and their capability of removing oil aerosols; Part 2 (2007) covers hydrocarbon vapour adsorbent filters, whose performance characteristics are adsorptive capacity and pressure drop. For the air itself, ISO 8573-1:2010 specifies purity classes of compressed air with respect to particles, water and oil, and ISO 8573-5:2025 specifies the test method for determining the oil vapour content.

Coalescing first, then carbon

The 2016 US Department of Energy sourcebook describes adsorbent filters as the filters for removal of odours and taste, and the 2026 fact sheet as the filters for vaporous contaminants. In the ULTRAK design the carbon stage comes after a coalescing stage: the datasheet says a coalescing filter is required upstream of the tower, and recommends a 1 µm dust filter downstream to intercept any residue from the activated carbon.

Gardner Denver's filter brochure adds a stage in front: water separators remove bulk liquids such as condensate, water and liquid oil by directional and centrifugal separation, and, installed before a coalescing filter, can protect it against bulk liquid contamination so that the filter operates more efficiently.

Where the oil comes from

The Compressed Air Challenge Fact Sheet #1 (May 2026) notes that lubricant-free air can be produced either with lubricant-free compressors or with lubricant-injected compressors that have additional separation and filtration equipment, and that this extra equipment causes some reduction in efficiency, especially if systems are not properly maintained.

For oil vapour, Ultra Controlo supplies the ULTRAK activated carbon tower: its datasheet gives a nominal residual oil vapour content below 0.003 mg/m³ and a pressure drop of 20 mbar when new and dry.

More questions

Will a coalescing filter remove oil vapour?

The Compressed Air Challenge Fact Sheet #11 (May 2026) lists coalescing filters for lubricant and moisture and adsorbent filters for vaporous contaminants, and ISO 12500 tests oil aerosols (Part 1) and oil vapours (Part 2) separately.

How is oil vapour content measured?

ISO 8573-5:2025 specifies the test method for determining the content of oil vapour in compressed air.

Sources

Ultra Controlo figures come from its technical datasheets. Third-party facts were read at the source on the date shown.

Reviewed: · Ultra Controlo engineering · Markdown version