Why is there water in compressed air lines?

Why is there water in the compressed air lines, and how do you stop it?

Short answer

The US Department of Energy compressed air sourcebook (third edition, 2016) explains that compressed air can no longer contain all the moisture possible at atmospheric conditions, so air leaving the aftercooler and separator is typically saturated and condenses more water as it cools in the piping; proper use of dryers avoids this.

Where the water comes from

Atmospheric air contains moisture, and the higher the air temperature, the more moisture it can hold, the sourcebook says. When air is compressed and occupies a smaller volume, it can no longer contain all of the moisture possible at atmospheric conditions, and some of it drops out as liquid condensate. Aftercoolers, installed after the final stage of compression, reduce the air temperature so that water vapour is condensed, separated, collected and drained, and a moisture separator is generally installed after each intercooler or aftercooler. Even so, air leaving an aftercooler and moisture separator is typically saturated, and further radiant cooling in distribution piping exposed to colder temperatures causes further condensation, with corrosion and contamination of point-of-use processes.

The sourcebook's Fact Sheet 6 describes a second route: a receiver placed before the dryer may give extra radiant cooling and drop out some condensate and entrained oil, but it is filled with saturated air, and a sudden demand above the capacity rating of the compressor and matching dryer can overload the dryer, resulting in a higher pressure dew point.

How to stop it

  • Dry the air. The sourcebook says the problem can be avoided by the proper use of compressed air dryers, and the Compressed Air Challenge Fact Sheet #11 (May 2026) says drying should only be performed to the degree the equipment and end use need.
  • Let receivers collect liquid. The fact sheet says receivers separate out particles and liquids, that in most systems the receiver is located before the dryer, and that a best practice is a wet receiver before the dryer and a dry receiver directly after it.
  • Keep the drains working. CAC Fact Sheet #5 (May 2026) says traps need periodic inspection: a trap stuck open leaks compressed air, and a trap stuck closed makes condensate back up and be carried downstream, where it can damage other system components. Fact Sheet #11 says leaving automatic traps partially open wastes substantial energy and should never be done, that a float drain that is not working should be cleaned and repaired, and that more reliable demand-type drain traps are worth considering where float drain maintenance is a burden.
  • Treat the condensate. Fact Sheet #11 says it is no longer acceptable to discharge condensate to sewer lines without treatment to remove contaminants such as entrained lubricants, except condensate from some lubricant-free compressor systems; condensate/lubricant separators work by settling tanks and/or permeable membranes.

The ULTRASEC datasheet describes the ULTRASEC as a refrigeration dryer with a hot gas bypass valve that keeps the dew point constant; see ULTRASEC.

More questions

Should drain traps be left slightly open?

No: CAC Fact Sheet #11 (May 2026) says leaving automatic condensate traps partially open wastes substantial energy and should never be done; a float drain that is not working should be cleaned and repaired.

Can compressor condensate go to the sewer?

CAC Fact Sheet #11 (May 2026) says it is no longer acceptable to discharge it to sewer lines without treatment to remove contaminants such as entrained lubricants, except condensate from some lubricant-free compressor systems.